HOWTO: Schneider PM9C quick install guide
Last Updated: Aug 23, 2012 06:41PM CEST
To follow this guide you will need:
-
1 x DEXGate
-
1 x PM9C
-
1 x USB-RS485 addapter
-
1 x Computer
-
1 x Ethernet Cable
Installation:
-
Install the current transformers following the following diagram:

-
Connect the orange usb cable to the D1 B/B' connector, the yellow cable to the D0 A/A' connector and the black cable to the 0V connector:

-
Power up the meter
-
Access to set up menu (pass: 0010)
-
Reset meter values
-
Select connection scheme
-
Configure current transformers factor
-
Verify bus speed (by default: 19200)
-
Configure ModBus address
-
Power up the DEXGate
-
Connect the USB-RS485 cable to the DEXGate
-
Connect the Ethernet cable to your computer and the ETH1 port of the DEXGate
-
Access the web administration interface of the DEXGate (http://172.16.0.1)
-
Login (the default username and password are admin/admin)
-
Go to the "Bridge Configuration" section
-
Edit the line:
devices.schneider-pm9c=
to look like this:
devices.schneider-pm9c=10
-
where "10" indicates ModBus meter adress
-
Save
-
Restart the modbus bridge or the DEXGate
-
You're done!