HOWTO: Schneider PM9C quick install guide

Last Updated: Aug 23, 2012 06:41PM CEST
To follow this guide you will need:
  • 1 x DEXGate
  • 1 x PM9C
  • 1 x USB-RS485 addapter
  • 1 x Computer
  • 1 x Ethernet Cable
Installation:
  1. Install the current transformers following the following diagram:
  2. Connect the orange usb cable to the D1 B/B' connector, the yellow cable to the D0 A/A' connector and the black cable to the 0V connector:
    Circutor cvm mini rs485
  3. Power up the meter
  4. Access to set up menu (pass: 0010)
  5. Reset meter values
  6. Select connection scheme
  7. Configure current transformers factor
  8. Verify bus speed (by default: 19200)
  9. Configure ModBus address
  10. Power up the DEXGate
  11. Connect the USB-RS485 cable to the DEXGate
  12. Connect the Ethernet cable to your computer and the ETH1 port of the DEXGate
  13. Access the web administration interface of the DEXGate (http://172.16.0.1)
  14. Login (the default username and password are admin/admin)
  15. Go to the "Bridge Configuration" section
  16. Edit the line:
    devices.schneider-pm9c=
    to look like this:
    devices.schneider-pm9c=10
  17. where "10" indicates ModBus meter adress
  18. Save
  19. Restart the modbus bridge or the DEXGate
  20. You're done!

Contact Us

  • Post a Public Question
  • Email Us
  • Tel : +34 931 810 195
    Hours: 9am - 6pm CEST, Mon to Fri
    support@dexmatech.com

    Check Public holidays here

    Support
support@dexma.com
http://assets0.desk.com/
false
dexma
Loading
seconds ago
a minute ago
minutes ago
an hour ago
hours ago
a day ago
days ago
about
false
Invalid characters found
/customer/en/portal/articles/autocomplete