DEXCell Energy Manager is compatible with the Schneider Com'X 510. In order to start receiving data to your account from your Com'X 510 follow this steps:
  1. In the upper right corner of your main page select "Settings ":
  2. Once in the Settings page select Gateways:
  3. Select "Register a new gateway":
  4. Select Com'X 510 and click "Next" :
     
  5. Choose a name for your Com'X 510 device and select "Schneider COMX 510" file format:
  6. Log into the Com'X 510 web interface and select Settings. Once inside Settings choose Publication.
  7. Select the following configuration:
    1. Destination platform: CSV export
    2. Publication Frequency: every hour
    3. Protocol: FTP
    4. Server: ftp.dexcell.com
    5. Port: 21
    6. User Login and Password: your username and password from the step 5
    7. Directory: leave this Empty
    8. Compression Activated: NO
    9. Field separator: Comma
    10. Decimal separator: Dot
    11. Date format: YYYY-MM-DDEGX300 dexcell energy manager configuration

#Note: Be sure that Periodic Publishing is ON